Victron VE.Direct serial sensor
victron_vedirect reads local VE.Direct text telemetry from a Victron charger or battery monitor through a compatible serial adapter. It does not support VE.Bus, query HEX registers, change charger settings, or create remote MeshCore/RF telemetry or RRD history. No serial bytes are transmitted by this plug-in.
Hardware testing: a community tester confirmed live readings on a Raspberry Pi, operation through /dev/serial/by-id/, an error when the USB cable was disconnected, and recovery with updating readings after reconnection. Restoring solar input also updated the readings to reflect charging. Automated tests separately use synthetic protocol fixtures and Linux pseudo-terminals. This validates the tested setup, not every Victron model, firmware, or adapter. Confirm that your connection is VE.Direct; use a suitable isolated VE.Direct-to-USB interface, not an unverified RS232/TTL cable. The official USB interface is described on protocol page 3. Port opening configures the host UART and uses the adapter/OS's normal control-line behavior; it is not a guarantee of electrically disconnected TX. For the official RS232 adapter, page 4 discusses DTR/RTS power requirements. Do not improvise controller pin wiring.
Install and configure
Install into the same Python environment used by the service, not an unrelated global Python:
sudo /opt/openhop_repeater/venv/bin/python -m pip install pyserial
The standard package already declares pyserial; this command is useful for minimal/custom installations. The sensor now uses SensorBase.ensure_python_modules during initialization, respecting the per-sensor/global auto_install_packages setting. If disabled, missing pyserial leaves the sensor unavailable; if enabled, the standard helper may install it during initialization. Type discovery remains safe without pyserial and never installs packages. Polling never runs pip or repeats dependency checks. Restart/reload the backend after resolving an initialization-time dependency failure.
On Raspberry Pi OS/Debian, check the device's ownership and grant the actual service account access to its group (normally dialout):
sudo usermod -a -G dialout repeater
# For an interactive reader, use your own login account instead:
# sudo usermod -a -G dialout "$USER"
Log out/in to refresh interactive group membership. A service must be restarted after its account's group membership or installed code changes. Use your installation's controlled restart procedure; do not solve permissions by running the daemon as root or making the port world-writable.
Stop cat /dev/ttyUSB0, serial monitors, Venus/GX readers, and any other program using the same port. Linux exclusive mode is advisory and cannot prevent a reader that ignores the lock from stealing bytes. Do not configure two sensor instances for one device. Each instance must have a unique name.
Add this under the existing sensors section (merge, do not replace other definitions):
sensors:
enabled: true
poll_interval_seconds: 10.0
auto_install_packages: false
definitions:
- type: victron_vedirect
name: solar-charger
enabled: true
auto_install_packages: false
settings:
serial_device: "/dev/serial/by-id/REPLACE_WITH_YOUR_ADAPTER"
read_timeout_seconds: 1.5
Use your real /dev/serial/by-id/ path to survive USB enumeration changes. /dev/ttyUSB0 is supported but can identify a different adapter after reboot. The settings API discovers this sensor automatically; installing the module does not detect hardware or add a definition. Restart after installing code, then add/configure it in Sensor Manager. Construction rejects a missing/nonlocal device path or invalid deadline, and SensorManager skips an invalid definition with a warning. The generic settings save API does not validate these plug-in-specific values before persistence.
read_timeout_seconds defaults to 1.5 and must be finite, between 0.05 and 2.0 seconds. Short values are useful in tests but can miss live frames, which arrive approximately once per second. Serial settings are fixed at 19200 baud, 8 data bits, no parity, 1 stop bit, no flow control. No baud-rate or write-command setting is offered.
Docker
Map the host adapter to a fixed device name inside the container and set the sensor's serial_device to that name. Grant the container process the host device group's numeric GID; do not assume dialout has the same GID inside and outside the image. Example Compose fragment, with placeholders replaced:
services:
repeater:
devices:
- "/dev/ttyUSB0:/dev/victron"
group_add:
- "REPLACE_WITH_HOST_DEVICE_GROUP_GID"
Resolve the host's by-id symlink before mapping, or use a stable host udev alias. Docker short device syntax uses colons as separators; do not use a by-id name containing colons unescaped. Use /dev/victron in container config. USB unplug/replug can require recreating the container's device mapping; the plug-in cannot repair Docker's host device binding. LXC likewise needs host device permissions and an explicit device bind/cgroup allowance.
Reading behavior and availability
Every poll opens the configured local port, reads for the bounded acquisition window, and closes it, including failure paths. There is no background serial owner or SensorManager lifecycle change. Reads request at most 256 bytes with at most 100 ms timeout, constrained by a monotonic deadline and 16 KiB total byte budget. Parser memory retains at most 2 KiB of stream suffix plus the checksum byte; field labels/values are limited to 8/32 ASCII characters and blocks to 22 data fields. Noise, oversized/malformed blocks, partial frames and checksum failures never contribute telemetry. Asynchronous colon-to-LF HEX messages are skipped without including their bytes in the text checksum; the checksum itself is one arbitrary binary byte, including colon, tab, CR, LF, NUL or high-bit bytes.
All complete validated blocks observed during this poll only are merged; the last observed value for a repeated field wins. Blocks are not an atomic hardware snapshot. A partial block at the deadline is discarded. Fields in unobserved blocks are unavailable, not copied from a previous poll. A disconnect/permission/read/close failure makes the entire reading unavailable, even if a valid block preceded the failure. The next poll opens afresh and can recover after reconnection.
Read latency can consume the configured deadline even on success. Other sensors in the manager wait behind this poll, but it does not wait indefinitely for a controller. Multiple configured serial devices add their bounded acquisition times. This deadline bounds normal local serial acquisition, not pathological kernel/driver failure or the existing manager's scheduling interval.
The standard envelope contains name, type, ok, timestamp, flat numeric/boolean data, optional error, and metrics. A validated text block gives ok: true even if no supported measurement is present. No valid frame gives ok: false and empty data. A present invalid field is null; a missing field is omitted. --- is unavailable, and TTG=-1 means infinite, represented as unavailable rather than a fabricated numeric duration. V1's metric descriptors retain the Measurements/Status grouping and units in the existing UI. Previously observed descriptors remain unavailable with a missing/invalid/read_failed reason; no previous value or decoded label is retained.
Only an explicit allowlist is published. Serial number (SER#), product/firmware strings, unknown labels, HEX payloads and raw frames are not returned or logged. Transport errors are deliberately sanitized.
Fields and units
Fields depend on model, firmware and configured auxiliary input. This table describes supported conversions, not a promise that a particular MPPT emits every field. In particular battery-monitor SOC, consumed Ah and battery temperature are not fabricated for an MPPT.
| Text labels | Flat keys | Output units / conversion |
|---|---|---|
V, I |
battery_voltage_v, battery_current_a |
mV→V, mA→A; current sign preserved |
VPV, PPV, IL |
pv_voltage_v, pv_power_w, load_current_a |
mV→V, W, mA→A |
Calculated from V and IL |
load_power_w |
Battery voltage (V) × load current (A) → W; Load power (calculated) in Measurements |
CS, ERR, MPPT |
charge_state_code, error_code, tracker_state_code |
Numeric codes; official descriptions in the corresponding card labels |
LOAD, Relay, Alarm |
load_output, relay, alarm |
Case-insensitive ON/OFF→boolean; other values unavailable |
AR, OR, MON |
alarm_reason, off_reason, monitor_mode_code |
Decimal alarm mask, hexadecimal off mask, signed monitor mode; decoded wording in card labels |
VS, VM, DM |
aux_voltage_v, midpoint_voltage_v, midpoint_deviation_percent |
mV→V, mV→V, per-mille→percent |
T, P, CE, SOC, TTG |
battery_temperature_c, battery_power_w, consumed_ah, state_of_charge_percent, time_to_go_minutes |
°C, W, mAh→Ah, per-mille→percent, minutes |
H1, H2, H3, H6 |
deepest_discharge_ah, last_discharge_ah, average_discharge_ah, cumulative_drawn_ah |
mAh→Ah; signs preserved |
H4, H5, H10, H11, H12 |
charge_cycles, full_discharges, automatic_syncs, low_voltage_alarms, high_voltage_alarms |
Counts |
H7, H8, H15, H16 |
min_battery_voltage_v, max_battery_voltage_v, min_aux_voltage_v, max_aux_voltage_v |
mV→V |
H9 |
seconds_since_full_charge |
Seconds |
H17, H18 |
history_energy_h17_kwh, history_energy_h18_kwh |
0.01 kWh→kWh; see mode caveat below |
H19, H20, H22 |
yield_total_kwh, yield_today_kwh, yield_yesterday_kwh |
0.01 kWh→kWh; total is user-resettable |
H21, H23, HSDS |
max_power_today_w, max_power_yesterday_w, day_sequence |
W, W, day sequence 0–364 |
H17/H18 mean discharged/charged energy for a BMV, but produced/consumed energy in DC monitor mode; their keys intentionally avoid assigning a meaning that requires knowing the mode. MON is available only on supporting firmware. SOC outside 0–1000 per-mille and HSDS outside 0–364 are treated as invalid. Negative unsigned status codes/masks are invalid; MON remains signed.
Calculated load power
VE.Direct does not provide a direct load-power field here. When both battery voltage and load current are valid in the current poll, the sensor calculates load_power_w = battery_voltage_v * load_current_a after merging that poll's validated blocks. This is an estimate using battery voltage, not a separately measured power value. Zero is a valid result and the current's sign is preserved. The calculated product is rounded to six decimal places, matching millivolt × milliamp input resolution and removing binary floating-point tails without adding trailing zeros. Missing or invalid inputs never reuse a previous value; a previously discovered calculated card becomes unavailable with the corresponding reason. Its descriptor uses /derived/load_power_w to identify a calculated local field, not a wire-protocol label. No UI or configuration change is required, and the existing V1 grouping remains intact.
Readable status values — sensor only
Keep V1's numeric codes, measurement units and Measurements/Status grouping. Decode statuses inside the sensor and append the wording to the existing descriptor's label: for example Charge state — Float above the unchanged value 5. This is a card-label change, not a new string value type or display_value contract. There are no extra flat label fields, duplicate cards, Legacy values section, UI dependency, or compatibility/version switch. Numeric measurements, codes and counts remain numbers; LOAD/Relay/Alarm remain booleans.
CS: official state of operation (p. 15), e.g.3→ Bulk.ERR: official error code (p. 15), e.g.0→ No error.MPPT: tracker operation (p. 16), e.g.2→ MPP Tracker active.MON: signed DC monitor mode (p. 16), e.g.-9→ Solar charger.OR: hexadecimal off-reason mask (p. 11), e.g.0x9→ No input power; Remote input.AR: decimal alarm-reason mask (p. 11), e.g.5→ Low Voltage; Low SOC.
Unknown enum values remain explicit as Unknown (code) in the label. All active mask reasons are included; unrecognized bits are appended as Unknown bits (0xHEX), not silently discarded. A zero reason mask's label includes None, meaning no reason bits are set (not an inference about device health). Missing/invalid/failed metrics keep only their plain field label and render n/a, never previous decoded wording. day_sequence remains numeric. These interpretations follow the protocol, not a guessed physical model.
For MPPT 75/15 and 100/15, firmware 1.14 and earlier reports converter output current in I, not necessarily current into the battery. Protocol Table I footnote 5 documents the distinction. This plug-in preserves the reported current; confirm firmware before treating that key as battery current on older models.
Authoritative protocol and implementation evidence
Source: Victron VE.Direct Protocol 3.34, document history dated 14 April 2025. Page numbers below are PDF pages (including the contents page).
| Authority | Implementation / tests |
|---|---|
p. 2, Introduction: text/HEX coexistence; asynchronous :A…LF may interrupt text |
VEDirectParser.feed; synthetic fragmented HEX-interleaved fixtures |
| p. 4, Serial port configuration | Fixed 19200 8N1, all flow control disabled; serial constructor assertion and real pyserial PTYs |
| p. 5, Message format, Data integrity: CRLF/label/tab/value, binary single-byte Checksum, modulo-256 sum=0, multiple blocks | Incremental binary parser; all 256 checksum byte values, corruption/resync and multiple-block polling tests |
| pp. 6–9, Fields, Table I Supported Text-mode fields | Explicit FIELDS conversion allowlist and parameterized real-manager normalization tests |
| p. 6 footnotes 8–11; p. 7 footnote 12 | --- invalid/unsynchronized/unsupported values and infinite TTG=-1 tests |
| pp. 10–11, I, Alarm, Relay, AR, OR; pp. 15–16, CS, ERR, HSDS, MPPT, MON | Preserve current sign; sensor-local decoding for all enum values and mask bits, unknown codes/bits and multi-reason tests in tests/test_victron_status.py; case-insensitive flags; no fabricated model fields |
| p. 17, Implementation guidelines | 8/32 character field payload bounds, 22 temporary data fields, validation before publication; bounded noise/malformed fixtures |
SensorBase.read/_reading_metrics, registry decorator, SensorManager.reload/read_all, APIEndpoints.sensors_types |
Real manager and settings-discovery tests; unchanged V1 descriptor contract; no new lifecycle hooks or UI contract |
All tests in tests/test_victron_vedirect.py are explicitly synthetic. PTYs exercise the real Linux/pyserial open/read/close path, fragmentation, timeout, disconnect/recovery and absence of transmitted serial data; they do not validate the friend's controller, cable, firmware or live values.